Closed Tank DP Level Transmitter Simulator – Dry Leg
How it works — beginner guide
- Tank pressure acts on the liquid surface.
- The HP port senses bottom pressure: vapor pressure + liquid head.
- The LP port connects to the vapor space through a dry leg (gas-filled, no condensate column).
- The transmitter subtracts LP from HP. The common vapor pressure cancels, leaving the liquid head.
For a gas density small compared with the liquid: DP (mmH₂O) ≈ SG × level (mm)
Process inputs — change and observe
Live transmitter outputs
| Actual liquid level | 1000 mm |
| Liquid head / DP | 1000 mmH₂O |
| Bottom pressure (HP) | 5.0981 bar(g) |
| Top pressure (LP) | 5.0000 bar(g) |
| Pressure difference (HP − LP) | 0.0981 bar |
| Calibrated DP span (0–100%) | 0–2000 mmH₂O |
| Measured level | 50.0% |
| 4–20 mA output | 12.00 mA |
Calibration & key terms
Level % = (measured DP ÷ calibrated DP span) × 100
Output mA = 4 + (16 × level % ÷ 100)
HP: High-pressure port connected to the tank bottom.
LP: Low-pressure port connected to vapor space via the dry leg.
SG: Liquid density compared with water. Higher SG produces more DP at the same level.
Closed Tank DP Level Measurement Using a Dry Leg
A differential pressure (DP) level transmitter is widely used to measure liquid level in pressurized closed tanks. Unlike an open tank, a closed tank contains vapor or gas pressure above the liquid. A DP transmitter uses high-pressure (HP) and low-pressure (LP) connections to measure the liquid level accurately.
How Does a Dry Leg DP Level Transmitter Work?
In a dry leg arrangement, the LP impulse line connects the transmitter to the vapor space at the top of the tank. The line remains filled with gas and does not contain a liquid condensate column.
- HP connection: Connected to the bottom of the tank to sense vapor pressure plus liquid head.
- LP connection: Connected to the top vapor space to sense vapor pressure.
- DP transmitter: Calculates the difference between HP and LP pressures.
The common vapor pressure cancels out, leaving the differential pressure generated by the liquid column.
DP Level Measurement Formula
The basic principle is:
DP = HP pressure − LP pressure
For a liquid with negligible gas-density effects:
DP (mmH₂O) ≈ Liquid SG × Level (mm)
For example, if the liquid level is 1,000 mm and its specific gravity (SG) is 1.0, the differential pressure is approximately 1,000 mmH₂O.
How Does Specific Gravity Affect Measurement?
Specific gravity represents the liquid density relative to water. At the same liquid level, a liquid with higher SG produces greater differential pressure. Therefore, the transmitter’s calibrated range must match the actual process liquid and tank measurement span.
Understanding the 4–20 mA Output
A level transmitter commonly uses a 4–20 mA signal:
- 4 mA: 0% calibrated level
- 12 mA: 50% calibrated level
- 20 mA: 100% calibrated level
Use the interactive simulator above to adjust liquid level, tank height, specific gravity, and vapor pressure, and observe how the calculated DP and output current change.
Dry Leg vs. Wet Leg
A dry leg is intended to remain gas-filled. If condensate accumulates in the reference line, it creates an additional liquid head and can cause measurement error. In services where condensation is expected, a wet-leg arrangement or another suitable measurement configuration may be required.
Practical Considerations
Before commissioning a DP level transmitter, verify the HP and LP connections, transmitter elevation, impulse-line routing, process-fluid density, and calibrated lower and upper range values (LRV and URV). Always follow the transmitter manufacturer’s instructions and the plant’s approved calibration procedure.
Note: This simulator demonstrates simplified measurement principles. Actual installations may require elevation and impulse-line corrections, as well as compensation for process-specific conditions.