Closed Tank DP Level Transmitter Simulator – Dry Leg

Closed Tank DP Level Transmitter — Dry Leg
CLOSED TANKVapor / gas spacePressure = Pₜₒₚ Liquid level 50%Process liquid HP (+)Bottom tap LP (−)Dry reference leg 50.0%12.00 mADP TRANSMITTERHP − LP = ΔP4–20 mA Bottom pressure: Pₜₒₚ + liquid headTop pressure reaches LP through dry legStatic gas pressure cancels out

How it works — beginner guide

  1. Tank pressure acts on the liquid surface.
  2. The HP port senses bottom pressure: vapor pressure + liquid head.
  3. The LP port connects to the vapor space through a dry leg (gas-filled, no condensate column).
  4. The transmitter subtracts LP from HP. The common vapor pressure cancels, leaving the liquid head.
DP = Pbottom − Ptop
For a gas density small compared with the liquid: DP (mmH₂O) ≈ SG × level (mm)
Dry leg assumption: the reference leg remains gas-filled and does not collect condensate. This example ignores gas density and impulse-line elevation effects.

Process inputs — change and observe

50%
mm
SG
bar(g)
Static pressure is included in both HP and LP readings to show why it cancels. Change level, tank height, or SG and watch the DP and current update.

Live transmitter outputs

Actual liquid level1000 mm
Liquid head / DP1000 mmH₂O
Bottom pressure (HP)5.0981 bar(g)
Top pressure (LP)5.0000 bar(g)
Pressure difference (HP − LP)0.0981 bar
Calibrated DP span (0–100%)0–2000 mmH₂O
Measured level50.0%
4–20 mA output12.00 mA
For this simplified calibration, 0% level = 4 mA and 100% level = 20 mA. The transmitter measures differential pressure, not the tank’s absolute pressure.

Calibration & key terms

DP span = SG × tank height
Level % = (measured DP ÷ calibrated DP span) × 100
Output mA = 4 + (16 × level % ÷ 100)

HP: High-pressure port connected to the tank bottom.

LP: Low-pressure port connected to vapor space via the dry leg.

SG: Liquid density compared with water. Higher SG produces more DP at the same level.

Real-plant caution: verify transmitter elevation, impulse-line routing, process-fluid properties, and the manufacturer’s LRV/URV calculation. If condensate forms in the dry leg, its liquid head can cause level error; some services require a wet leg instead.

Closed Tank DP Level Measurement Using a Dry Leg

A differential pressure (DP) level transmitter is widely used to measure liquid level in pressurized closed tanks. Unlike an open tank, a closed tank contains vapor or gas pressure above the liquid. A DP transmitter uses high-pressure (HP) and low-pressure (LP) connections to measure the liquid level accurately.

How Does a Dry Leg DP Level Transmitter Work?

In a dry leg arrangement, the LP impulse line connects the transmitter to the vapor space at the top of the tank. The line remains filled with gas and does not contain a liquid condensate column.

  • HP connection: Connected to the bottom of the tank to sense vapor pressure plus liquid head.
  • LP connection: Connected to the top vapor space to sense vapor pressure.
  • DP transmitter: Calculates the difference between HP and LP pressures.

The common vapor pressure cancels out, leaving the differential pressure generated by the liquid column.

DP Level Measurement Formula

The basic principle is:

DP = HP pressure − LP pressure

For a liquid with negligible gas-density effects:

DP (mmH₂O) ≈ Liquid SG × Level (mm)

For example, if the liquid level is 1,000 mm and its specific gravity (SG) is 1.0, the differential pressure is approximately 1,000 mmH₂O.

How Does Specific Gravity Affect Measurement?

Specific gravity represents the liquid density relative to water. At the same liquid level, a liquid with higher SG produces greater differential pressure. Therefore, the transmitter’s calibrated range must match the actual process liquid and tank measurement span.

Understanding the 4–20 mA Output

A level transmitter commonly uses a 4–20 mA signal:

  • 4 mA: 0% calibrated level
  • 12 mA: 50% calibrated level
  • 20 mA: 100% calibrated level

Use the interactive simulator above to adjust liquid level, tank height, specific gravity, and vapor pressure, and observe how the calculated DP and output current change.

Dry Leg vs. Wet Leg

A dry leg is intended to remain gas-filled. If condensate accumulates in the reference line, it creates an additional liquid head and can cause measurement error. In services where condensation is expected, a wet-leg arrangement or another suitable measurement configuration may be required.

Practical Considerations

Before commissioning a DP level transmitter, verify the HP and LP connections, transmitter elevation, impulse-line routing, process-fluid density, and calibrated lower and upper range values (LRV and URV). Always follow the transmitter manufacturer’s instructions and the plant’s approved calibration procedure.

Note: This simulator demonstrates simplified measurement principles. Actual installations may require elevation and impulse-line corrections, as well as compensation for process-specific conditions.